Protection class
overview VDE 0710 after DIN 40050 |
First code digit
|
Meaning for the protection operational funds |
Second code digit
|
Waterproof |
0
|
not protected |
0
|
not protected |
1
|
Protection against penetration of solid foreign bodies with a diameter > 50 mm |
1
|
Protection against perpendicularly dripping water |
2
|
Protection against penetration of solid foreign bodies with a diameter >
12.5 mm |
2
|
Protection against dripping water with 15° inclination |
3
|
Protection against penetration of solid foreign bodies with a diameter >2.5 mm |
3
|
Protection against spray waters
|
4
|
Protection against penetration of solid foreign bodies with a diameter >
1 mm |
4
|
Protection against splash-water |
5
|
dust protected |
5
|
Protection against jet water |
6
|
dustproof |
6
|
Protection against strong jet water |
|
|
7
|
Protection against temporary submerging |
|
|
8
|
Protection against continuous submerging |