EE 65 air flow transducer
transducer to measure air flow velocity / with optinal display / thin film technology / wall-mounted or pipe-mounted |
|
The EE 65 air flow transducer is used to perform accurate measurents of air flow velocity within heating, ventilation and air-conditioning sectors. Thanks to its compact design the EE 65 air flow transducer can be used
almost in any field of application. EE 65 ir flow transducer has an omnidirectional sensor with a modern thin film technology which makes the sensor head resistant against dust and dirt. Apart from measuring air flow velocity, the EE 65 air flow transducer transmits a normalized signal of 4-20 mA or a voltage one of 0-10 V. The users can set the measurement range, output signal and response time according their needs, therefore the sensor can be freely adjusted. The EE 65 air flow transducer can be wall mounted or pipe mounted by means of a mounting flange. Sensors can be fixed-mounted or displaced by a connection cable, so the EE 65 air flow transducer has a wide field of application
within the heating, ventilation and air-conditioning systems. At the following
link you will find the air flow transducer that best suits your needs. |
|
View / print user's manual
of the EE 65 air flow transducer
 |
|
- Omnidirectional
- Easy installation
- Wall or pipe mounted |
- Individual use
- Thin film anemometer
- High accuracy |
|
Technical specifications |
|
Air velocity |
| Measurement Range |
0 ... 1 m/s
0 ... 1,5 m/s
0 ... 2 m/s |
| Accuracy (in the air at 25 ºC, 45 % r.H., 1013 hPa) |
0.15 ... 1 m/s: ±(0,04 m/s + 2 % of the
measurement value.)
0,15 ... 1,5 m/s: ±(0,05 m/s + 2 % of the
measurement value.)
0,15 ... 2 m/s: ±(0,6 m/s + 2 % of the measurement value.) |
| Response time T90 |
4 s or 0,2 s |
|
General information |
|
Power supply voltage |
24 V DC/AC ±20% |
|
Input current |
max. 160 mA wiht AC power supply
max. 90 mA with DC power supply |
|
Connections |
Screw terminal max. 1 mm2 |
|
Electromagnetic compatibility |
EN61326-1; EN61326-2-3 |
|
Material |
Polycarbonate |
|
Protection |
IP65, with IP 40 display |
|
Operating temperature: Sensor |
-25 ... 50 ºC |
|
Operating temperature: electronics |
-10 ... 50 ºC |
|
Storage temperature |
-30 ... 60 ºC |
|
Connections |
 |
|
Dimensions |
|
 |
Delivery contents
1 x EE 65 air flow transducer and user's manual |
 |
 |
|
Here you will find an overview of all the measuring instruments
available at PCE Instruments. |
|
Contact:
PCE Instruments UK Limited
Units 12/13 Southpoint Business Park
Ensign Way, Southampton
United Kingdom, SO31 4RF
Phone. +44 ( 0 ) 2380 98703 0
Fax +44 ( 0 ) 2380 98703 0 |
|
This
page in German
in Italian
in Spanish
in Croatian
in French
 |